Hioki pull-through AC/DC current sensors are best-in-class devices for use with power meters, Memory HiCorders and high performance oscilloscopes.
The CT6863 is a DC to 500kHz/200A sensor, and this is ideal for capturing current signals from switching power supplies, inverters, power conditioners, etc. CAT III 1000 V
Basic specifications (Accuracy guaranteed for 1 year, Post-adjustment accuracy guaranteed for 1 year)
Rated current |
200 A AC/DC |
Max. allowable input |
400 A rms (requires derating) |
Frequency characteristics |
Amplitude: DC to 500 kHz
Phase: DC to 300 kHz |
Amplitude and Phase accuracy |
DC ±0.05 % rdg. ±0.01 % f.s. (Phase: Not defined)
16 Hz ≤ f ≤ 400 Hz ±0.05 % rdg. ±0.01 % f.s. (Phase: ±0.2°)
Defined to 500 kHz |
Output voltage |
2 V /rated current value
(voltage output with the Sensor Unit, use with a device having a 1 MΩ input resistance or higher) |
Max. rated voltage to earth |
AC/DC 1000 V (50/60 Hz, CAT III ) |
Core diameter |
φ 24 mm (0.94 in) |
Operating temperature, humidity |
-30°C to +85°C (-22°F to 185°F), 80% RH or less (with no condensation) |
Power supply |
±11 V to ±15 V DC (Power suppled via the Sensor Unit, which supports 100 to 240 V AC) |
Power consumption |
6 VA max. (at 200 A/55 Hz, ±12 V power requirement) |
Dimensions and mass |
70 mm (2.76 in)W × 100 mm (3.94 in)H × 53 mm (2.09 in)D, 350 g (12.3 oz), cord length: 3 m (9.84 ft) |
Accessories |
Instruction manual ×1, Mark bands ×6 |
Compatible models...CT6863 (-05)
Compatible models |
CT6863 |
CT6863-05 |
Power Analyzer PW6001, PW3390 |
△ (Requires CT9900) |
OK |
Power Analyzer 3390 |
OK |
△ (Requires CT9901) |
Power HiTester 3193 series |
OK |
△ (Requires CT9901) |
Current Unit 8971 |
△ (Requires the 9318) |
△ (Requires the 9318, CT9901) |
F/V Unit 8940 |
△ (Requires the 9318, 9705) |
△ (Requires the 9318, 9705, CT9901) |